50kVA-350kVA
480V
Compact high-capacity, energy-efficient 480V modular UPS for data centers, industrial, and medical systems
Scalable Modular Three-Phase UPS · 480V · 50–350 kW
A scalable, modular 480V online double-conversion UPS for mission-critical data center, industrial, and medical environments. Built around hot-swappable 50 / 70 kW power modules, the X90-5S scales from 50 to 350 kW, pairs with external X90-BC battery cabinets for flexible runtime, and offers an optional SMB-350 slim maintenance bypass for service without downtime.
↓ Download the X90-5S datasheet (PDF)
The X90-5S is built around hot-swappable power modules in a five-slot frame, scaling from 50 kW up to 350 kW (5 × 70 kW) — or up to 250 kW with 50 kW modules. Capacity grows by adding modules as load requirements change, with N+1 redundancy configured within installed slot capacity. Full front access means no rear clearance is required for installation or service, and runtime is provided by external X90-BC modular battery cabinets (or compatible third-party battery systems) for flexible, scalable runtime.
Runtime lives in the X90-BC — a matching external battery cabinet that holds up to 36 hot-swappable battery modules behind a front battery disconnect, with a second cabinet extending capacity to 72 modules. Because the batteries are external and modular, the X90-BC supports a range of chemistries — VRLA (lead-acid), lithium-ion, nickel-zinc, and sodium-ion — so runtime, cycle life, footprint, and temperature range can be matched to the site rather than fixed by the UPS.
For service and repair without dropping the load, the X90-5S also pairs with the optional SMB-350 — a slim, matching maintenance-bypass cabinet just 11.8 inches wide. Rated to 65 kAIC, it provides a manual maintenance bypass (Q1 main, Q2 maintenance bypass, Q3 output) in the most compact footprint, enabling safe full-system service with the load powered.
Add hot-swappable power modules as load grows — capacity scales from 50 kW to 350 kW within a single five-slot frame.
Configurable with N+1 redundant power and battery modules for continuous uptime.
Replace power modules without system interruption — service while the load stays protected.
Pairs with X90-BC modular battery cabinets or compatible third-party battery systems for flexible runtime.
Slim, matching maintenance-bypass cabinet enables safe service and repair while maintaining load power.
Up to 96.5% in online mode and 99% in ECO mode, reducing energy cost in continuous duty.
No rear clearance required for installation or maintenance — supports against-wall and tight-room installs.
Top or bottom cable entry for easy integration in any electrical room.
Separate rectifier and bypass feeds, or a single input, for maximum installation flexibility.
Real-time graphic display of system status and alarms.
High short-circuit withstand for demanding industrial environments.
X90-5S is the modular, externally-batteried enterprise platform within the X90 family — used in data centers, industrial automation, medical imaging, and modular infrastructure that needs scalable capacity and redundancy beyond a single integrated cabinet. The family scales on a shared architecture:
You are here
See the full platform: X90 Modular UPS Series →
Large-scale UPS protection has traditionally meant fixed-capacity systems sized for peak load on day one. The X90-5S scales on a modular frame — add power modules as load grows and external X90-BC cabinets as runtime needs change — so capital is matched to actual capacity. Hot-swappable modules and the optional SMB-350 bypass keep the system serviceable without downtime.
Compare the X90-5S against platforms such as the Eaton 93PM: X90-5S UPS comparisons →
The X90-5S uses external X90-BC modular battery cabinets for flexible, scalable runtime. One X90-BC supports up to 36 battery modules; a second X90-BC extends capacity to 72 modules. The modular architecture supports redundancy and serviceability through hot-swappable power and battery modules, allowing maintenance without system downtime.
| Load ↓ / modules → | X90-5S + 1 × X90-BC | X90-5S + 2 × X90-BC | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 16 | 20 | 24 | 28 | 32 | 36 | 40 | 44 | 48 | 52 | 56 | 60 | 64 | 68 | 72 | |
| 70 kW | 8 | 10 | 13 | 16 | 19 | 22 | 25 | 28 | 31 | 34 | 38 | 41 | 44 | 48 | 51 |
| 140 kW | – | – | – | 6 | 8 | 9 | 10 | 12 | 13 | 15 | 16 | 18 | 19 | 21 | 22 |
| 180 kW | – | – | – | – | 5 | 6 | 7 | 8 | 10 | 11 | 12 | 13 | 14 | 15 | 16 |
| 210 kW | – | – | – | – | – | – | 6 | 7 | 8 | 9 | 10 | 10 | 11 | 12 | 13 |
| 280 kW | – | – | – | – | – | – | – | – | – | 5 | 6 | 7 | 8 | 8.5 | 9 |
| 300 kW | – | – | – | – | – | – | – | – | – | – | 5 | 6 | 7 | 7.5 | 8 |
| 350 kW | – | – | – | – | – | – | – | – | – | – | – | – | 5 | 6 | 6.5 |
Runtimes in minutes; vary with battery age and site conditions. Columns 16–36 use a single X90-BC cabinet; the shaded columns (40–72) require a second X90-BC. Load rows include 180 and 300 kW operating points that fall between catalog model ratings. For longer runtimes or custom battery configurations, contact sales. N+1 redundancy is configured within installed slot capacity and is not implied at a frame’s fully-populated maximum.
| Model | Power modules | Power rating | Charge current |
|---|---|---|---|
| X90-5S50k | 1 × 50 kW | 50 kW | 18 A |
| X90-5S70k | 1 × 70 kW | 70 kW | 18 A |
| X90-5S100k | 2 × 50 kW | 100 kW | 36 A |
| X90-5S140k | 2 × 70 kW | 140 kW | 36 A |
| X90-5S150k | 3 × 50 kW | 150 kW | 54 A |
| X90-5S200k | 4 × 50 kW | 200 kW | 72 A |
| X90-5S210k | 3 × 70 kW | 210 kW | 54 A |
| X90-5S250k | 5 × 50 kW | 250 kW | 90 A |
| X90-5S280k | 4 × 70 kW | 280 kW | 72 A |
| X90-5S350k | 5 × 70 kW | 350 kW | 90 A |
For enterprise and data-center loads beyond 350 kW, the X90-10S extends the same modular, front-serviceable architecture to a larger frame — scaling up to 700 kW while retaining hot-swappable modules and external battery flexibility.
Deploying in a healthcare or imaging facility? See UPS for medical imaging — or, for MRI specifics, UPS for MRI systems.
Xtreme Power Conversion supports engineers, consultants, and facility operators with UPS sizing, infrastructure design, and system-modernization planning.
| MODEL NUMBER | X90-5S50k | X90-5S70k | X90-5S100k | X90-5S140k | X90-5S150k | X90-5S200k | X90-5S210k | X90-5S250k | X90-5S280k | X90-5S350k | |
| CAPACITY | Power rating | 50kW | 70kW | 100kW | 140kW | 150kW | 200kW | 120kW | 250kW | 280kW | 350kW |
| CABINET | X90-5S UPS: power modules | Up to 350kW (5 x 70kW) or up to 250kVA (5 x 50kW) | |||||||||
| X90-BC: battery modules | Up to 36 battery modules | ||||||||||
| INPUT | Voltage / frequency nominal | 480VAC (3W), 50/60Hz auto-sensing | |||||||||
| Voltage / frequency range | 329 – 520VAC (L-L), 40–70Hz | ||||||||||
| OUTPUT | Voltage | 480VAC (3W) | |||||||||
| Frequency | 40–70Hz | ||||||||||
| Efficiency | Up to 96.5% online mode or 99% ECO mode | ||||||||||
| Overload capacity | 105%-110% for 60min; 110%-125% for 10min; 126%-150% for 1min; >150% for 200ms | ||||||||||
| BATTERY SYSTEM | Nominal voltage | +/-240VDC | |||||||||
| Charge Current (programmable) | 18A | 36A | 54A | 72A | 90A | ||||||
| DIMENSIONS & | UPS & BC enclosure (W x D x H) | 31.5 x 42 x 79 in 787 lbs (UPS) / 23.6 x 42 x 79 in 838 lbs (BC) | |||||||||
| WEIGHTS | Bypass enclosure (W x D x H) | 11.8 x 42 x 79 in / 400 lbs | |||||||||
| Power & battery module | 17.2 x 29.5 x 5.1 in / 97 lbs (PM) 17.2 x 31.2 x 5.25 in / 73 lbs (BM) | ||||||||||
| ENVIRONMENT | Temperature | 0–40°C (32–104°F) | |||||||||
| Altitude | 5,200 ft above sea level | ||||||||||
| Audible noise (typical) | < 69dBA at 1m | ||||||||||
| APPROVALS | UL-1778, cUL, FCC A, RoHS, TAA, Energy Star | ||||||||||
| WARRANTY | 2 years (USA and Canada) | ||||||||||
| COMMUNICATIONS INTERFACE | RS-232, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus) | ||||||||||
| INCLUDED IN BOX | User manual, RS-232 cable, unloading ramp, ViewPower Software | ||||||||||
| AVAILABLE OPTIONS | External maintenance bypass, battery temperature sensor | ||||||||||