1000–3000 VA | 208–240V | 1U Online Double Conversion
High-density lithium rack UPS engineered for global IT, telecommunications, AV, and industrial infrastructure requiring conditioned power, compact deployment, and remote power control in 208–240V environments.
1U Rack · Online Double-Conversion · LiFePO₄ · 208–240V · 1–3kVA
Online double-conversion power protection in a 1U form factor with LiFePO₄ battery chemistry — up to 15-year service life, 50°C operation, individual outlet control, and external battery pack support on 2kVA and 3kVA models. The premium 1U lithium rack UPS for global IT, telecommunications, AV, and industrial infrastructure operating on 208–240V single-phase power.
The J90i continuously regenerates output power through the inverter — the connected load never operates on raw utility power. No transfer delay during a power event. Output power is clean, regulated, and isolated from upstream disturbances regardless of input conditions.
LiFePO₄ (lithium iron phosphate) batteries are rated for 3,000–5,000 discharge cycles and up to 15 years service life in ideal conditions. Across distributed deployments with 20 or 50 UPS units, eliminating the 3–5 year VRLA replacement cycle is a significant operational and cost advantage.
IDF closets, telecom rooms, and industrial enclosures regularly exceed 35–40°C. VRLA batteries specified at 25°C degrade rapidly above 30°C. The J90i delivers full rated output to 50°C (122°F) with no capacity derating — a 3kVA unit is still a 3kVA unit at 122°F. Warranty terms differ for continuous operation above 40°C.
Each outlet is individually switchable — a frozen switch, a hung firewall, a crashed controller can be power-cycled remotely without dispatching a technician. Across a campus with 20 IDF locations, that capability pays for itself after the first avoided service call.
The J90i-2kLiD and J90i-3kLiD support up to six EBP48 external LiFePO₄ battery packs for extended runtime — without the size and weight of VRLA battery cabinets. See the full runtime table below for exact values by load and pack count.
The J90i occupies 1U in a standard rack and mounts on any wall with the included bracket hardware. In IDF closets with wall-mount racks, the J90i installs clean without adapters or additional hardware — same unit, same bracket, either deployment.
Remote On/Off and Remote Power Off contacts start and shut down the UPS from a dry contact, independent of the network card. That covers emergency power-off interlocks and building-system sequencing, and it works whether or not an SNMP card is fitted.
In the USA and Canada, the J90i carries a $50,000 load protection policy covering equipment connected to the UPS. For an edge or telecom rack holding switches, controllers and processors, that is coverage on the load rather than just on the UPS.
J90i is the premium choice in 208–240V environments when 1U density, individual outlet control and lifecycle performance are the priorities. The P91g Li sits below it as the runtime-focused 2U option; the J60Ci when depth is the constraint; the J60i for ultra-compact standby duty. For 120V deployments see the J90.
Engineers standardizing 208–240V rack power most often compare the J90i against the APC Smart-UPS Ultra and the Tripp Lite (Eaton) SmartOnline series. All three are 1U online double-conversion platforms, so form factor is parity — the J90i’s differentiation is LiFePO₄ chemistry and lifecycle, 50°C thermal rating, individual per-outlet control, and warranty term.
| Feature | J90i | APC Smart-UPS Ultra | Tripp Lite (Eaton) SmartOnline |
|---|---|---|---|
| Form factor | 1U | 1U | 1U |
| Topology | Online double-conversion | Online double-conversion | Online double-conversion |
| Battery chemistry | LiFePO₄ | Lithium-ion | VRLA |
| Individual outlet control | Yes — per outlet | No | Switched load banks |
| External battery support | Yes — 2kVA and 3kVA | Yes | Yes |
| Max operating temp | 50°C | 40°C typical | 40°C typical |
| Wall mount | Yes — brackets included | Yes | Optional |
| TAA compliant | Yes | Model-dependent | Model-dependent |
| Warranty | 6 years | 5 years | 2 years |
Competitor specifications vary by model, SKU, and region; verify against current manufacturer documentation. Comparison reflects the 208–240V variants most often cross-shopped with the J90i.
By model: J90i-2kLiD vs APC SRTL2K2RM1UWC · J90i-3kLiD vs APC SRTL3KRM1UWC · J90i-1.5kLiD vs Tripp Lite SUINT1500LCD1U · J90i-2kLiD vs Tripp Lite SUINT2000LCD1U
| Attribute | J90i Series |
|---|---|
| Topology | Online double-conversion |
| Capacity | 1000VA / 1500VA / 2000VA / 3000VA |
| Input voltage | 208 / 220 / 230 / 240V AC · 40–70 Hz · C14 / C20 inlet |
| Output voltage | 208 / 220 / 230 / 240V AC · see the user manual for capacity at 208V output |
| Receptacles | (4) IEC C13 · 3kVA: (3) C13 + (1) C19 — all switchable |
| Frequency | 50/60 Hz auto-sensing |
| Efficiency | Online mode — up to 92% (1kVA and 1.5kVA) · 93% (2kVA) · 94.5% (3kVA) · ECO mode >96% (all models) |
| Battery chemistry | LiFePO₄ (lithium iron phosphate) |
| Battery service life | Up to 15 years — ideal conditions · 3,000–5,000 cycles |
| Operating temperature | Full rated output to 50°C (122°F) with no capacity derating · warranty terms differ for continuous operation above 40°C |
| Form factor | 1U rackmount |
| Dimensions (W×D×H) | 1kLiD: 17.2 × 18.8 × 1.7 in (438 × 477 × 44 mm) · 1.5kLiD: 17.2 × 20.1 × 1.7 in (438 × 511 × 44 mm) · 2kLiD / 3kLiD: 17.2 × 22.8 × 1.7 in (438 × 579 × 44 mm) |
| Weight | 1kLiD: 26.8 lb (12.2 kg) · 1.5kLiD: 27.7 lb (12.6 kg) · 2kLiD: 34.1 lb (15.5 kg) · 3kLiD: 35.2 lb (16 kg) |
| Internal battery | LFP 25.6V / 6Ah (1kVA) · 38.4V / 6Ah (1.5kVA) · 51.2V / 5Ah (2kVA and 3kVA) |
| Typical recharge | 4 hours (1kVA and 1.5kVA) · 1 hour (2kVA and 3kVA) |
| EBP48 battery pack | 17.2 × 22.8 × 1.7 in (438 × 579 × 44 mm) · 30.8 lb (14 kg) |
| Overload capacity | ≤130% for 2 min · 130–200% for 10 s · >200% for 250 ms |
| Altitude | Up to 6,500 ft (2,000 m) |
| Mounting | Rack or wall — brackets included standard |
| Outlet control | Individual switchable outlets |
| Extended runtime | External EBP48 packs — 2kVA and 3kVA models (up to 6 packs) |
| Monitoring | Optional SNMP/Web card |
| Communication | USB · RS-232 · optional SNMP |
| Remote contacts | ROO (remote on/off) and RPO (remote power off) dry contacts, independent of the SNMP card |
| Load protection | $50,000 connected-equipment protection policy (USA and Canada) |
| Warranty | 6 years — USA and Canada · 2 years above 40°C continuous · 2 years depot outside the USA and Canada |
| Certifications | UL-1778 · cUL · UN38.3 · RoHS · FCC Class A · TAA compliant |
Runtime values are estimated minutes at the load shown. Internal battery only for 1kVA and 1.5kVA models. The 2kVA and 3kVA models support up to six EBP48 external battery packs. Actual runtime varies by battery age, temperature, and load profile.
| Model / Configuration | 100VA 90W |
150VA 135W |
200VA 180W |
300VA 270W |
400VA 360W |
600VA 540W |
800VA 720W |
1000VA 900W |
1200VA 1080W |
1400VA 1260W |
1500VA 1350W |
1600VA 1440W |
1800VA 1620W |
2000VA 1800W |
2333VA 2100W |
2666VA 2400W |
3000VA 2700W |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| J90i-1kLiD | 53 | 35 | 30 | 21 | 16 | 11 | 8.1 | 6.5 | — | — | — | — | — | — | — | — | — |
| J90i-1.5kLiD | — | 59 | 44 | 33 | 24 | 17 | 13 | 10.5 | 8.8 | 7.5 | 7 | — | — | — | — | — | — |
| J90i-2kLiD | — | — | 54 | 36 | 28 | 20 | 15 | 12 | 10 | 8.6 | 8 | 7.5 | 6.7 | 6 | — | — | — |
| J90i-2kLiD + 1 EBP48 | — | — | 270 | 180 | 142 | 100 | 75 | 60 | 50 | 43 | 40 | 38 | 33 | 30 | — | — | — |
| J90i-2kLiD + 2 EBP48 | — | — | 486 | 324 | 255 | 180 | 135 | 108 | 90 | 77 | 72 | 68 | 60 | 54 | — | — | — |
| J90i-2kLiD + 3 EBP48 | — | — | 703 | 468 | 368 | 260 | 195 | 156 | 130 | 111 | 104 | 98 | 87 | 78 | — | — | — |
| J90i-2kLiD + 4 EBP48 | — | — | 919 | 613 | 481 | 340 | 255 | 204 | 170 | 146 | 136 | 128 | 113 | 102 | — | — | — |
| J90i-2kLiD + 5 EBP48 | — | — | 1135 | 757 | 594 | 420 | 315 | 252 | 210 | 180 | 168 | 158 | 140 | 126 | — | — | — |
| J90i-2kLiD + 6 EBP48 | — | — | 1351 | 901 | 708 | 500 | 375 | 300 | 250 | 214 | 200 | 188 | 167 | 150 | — | — | — |
| J90i-3kLiD | — | — | — | 38 | 28 | 20 | 15 | 12 | 10 | 8.6 | 8 | 7.5 | 6.7 | 6 | 5.1 | 4.5 | 4 |
| J90i-3kLiD + 1 EBP48 | — | — | — | 189 | 142 | 98 | 73 | 60 | 50 | 43 | 40 | 38 | 33 | 30 | 26 | 23 | 20 |
| J90i-3kLiD + 2 EBP48 | — | — | — | 341 | 256 | 176 | 132 | 108 | 90 | 77 | 72 | 68 | 60 | 54 | 46 | 41 | 36 |
| J90i-3kLiD + 3 EBP48 | — | — | — | 492 | 369 | 254 | 191 | 156 | 130 | 111 | 104 | 98 | 87 | 78 | 67 | 59 | 52 |
| J90i-3kLiD + 4 EBP48 | — | — | — | 644 | 483 | 333 | 249 | 204 | 170 | 146 | 136 | 128 | 113 | 102 | 87 | 77 | 68 |
| J90i-3kLiD + 5 EBP48 | — | — | — | 795 | 596 | 411 | 308 | 252 | 210 | 180 | 168 | 158 | 140 | 126 | 108 | 95 | 84 |
| J90i-3kLiD + 6 EBP48 | — | — | — | 946 | 710 | 489 | 367 | 300 | 250 | 214 | 200 | 188 | 167 | 150 | 129 | 113 | 100 |
All values in estimated minutes. Actual runtime varies by battery age, ambient temperature, and load profile. Download runtime PDF → · UPS sizing tool →
Sizing, runtime planning, EBP48 pack configuration, TAA procurement support, and deployment guidance for global 208–240V and distributed infrastructure.
Input voltage. The J90 is the 120 V platform; the J90i is the 208-240 V equivalent for racks and regions fed at higher voltage. Same 1U form factor, same LiFePO4 chemistry, same online double-conversion topology and per-outlet control. Choose on the supply at the rack, not on features.
Because most of them are not. IDF closets, telecom rooms and industrial enclosures regularly sit at 35-40 C, and VRLA batteries specified at 25 C degrade rapidly above 30 C. The J90i’s LiFePO4 chemistry and thermal design are rated to 50 C, which covers the real range of rack environments rather than the ideal one. On a distributed estate this is usually what decides battery service life.
LiFePO4 cells are rated for 3,000 to 5,000 discharge cycles and up to 15 years service life in ideal conditions. The practical comparison is against the 3 to 5 year VRLA replacement cycle. Across 20 or 50 sites, eliminating that cycle removes both the parts cost and the site visit, which is usually the larger number.
Remote recovery without a truck roll. Each outlet is independently switchable, so a frozen switch, a hung firewall or a crashed controller can be power-cycled from wherever you are. Across a campus with 20 IDF locations, that capability typically pays for itself after the first avoided service call. Neither the APC Smart-UPS Ultra nor the Tripp Lite SmartOnline offers per-outlet control in this class.
Yes, on the 2 kVA and 3 kVA models. The J90i-2kLiD and J90i-3kLiD support up to six EBP48 external LiFePO4 battery packs, without the size or weight of VRLA battery cabinets. The runtime table on this page gives exact figures by load and pack count.
Yes, and the brackets are included rather than optional. It occupies 1U in a standard rack or mounts on any wall with the supplied hardware. In IDF closets with wall-mount racks it installs without adapters or additional parts, so the same unit and the same bracket cover either deployment.
Yes, across the range. That matters on federal, state, education and healthcare contracts, where TAA eligibility on competing 1U platforms is model-dependent rather than standard.
Six years in the USA and Canada, covering electronics and battery, reducing to two years where the unit runs continuously above 40 C. Outside the USA and Canada, the warranty is two years, depot repair. Six years is longer than the APC Smart-UPS Ultra at five and the Tripp Lite SmartOnline at two.