Li90 · 30kVA / 30kW · Three-Phase Lithium · 208/120V · Slimmest 30kVA Available

Li90 30kVA — slimmest and lightest 30kVA lithium UPS for retrofit and space-constrained installations

The Li90 30kVA is the slimmest and lightest 30kVA lithium UPS available — 12.6″ wide and approximately 483 lbs. It delivers full 30kW three-phase power with integrated LiFePO₄ batteries in a single compact cabinet, designed specifically for retrofit installations and space-constrained electrical environments where traditional 30kVA VRLA UPS systems cannot fit or exceed floor-loading limits.

Li90 30kVA three-phase lithium UPS with battery door open, showing the three integrated hot-swappable LiFePO4 battery modules in a single cabinet
A single slim cabinet where a conventional 30kVA VRLA system would require a UPS plus external battery cabinets — consuming far more floor space
30kW
Output capacity
208/120V three-phase
12.6″
Cabinet width
narrowest 30kVA available
~483
System weight (lbs)
vs 900–1,500 lbs VRLA
50°C
Max operating temp
no derating to 40°C
15 yr
Battery service life
ideal conditions · LiFePO₄
Retrofit and Space-Constrained Installations

Designed for locations where conventional 30kVA UPS systems cannot fit

Legacy 30kVA VRLA UPS systems are typically wide, heavy, and dependent on external battery cabinets. The Li90 was engineered to replace these installations in constrained electrical rooms, telecom shelters, and edge deployments — combining the power electronics and lithium batteries in a single cabinet that fits through standard doors and service aisles.

12.6″

Cabinet width — narrowest 30kVA available

Fits through standard doors. Installs in aisles where 24–36″-wide conventional systems cannot maneuver or fit at the installation site.

~483

System weight (lbs) — dramatically lower floor loading

Conventional 30kVA VRLA systems weigh 900–1,500 lbs combined with battery cabinets. Li90 reduces floor loading, seismic anchoring requirements, and installation rigging cost.

0

External battery cabinets required

LiFePO₄ batteries integrate inside the UPS enclosure — no separate battery frames, no additional floor-space allocation, and no additional electrical connections for battery cabinets.

50°C

Operating temperature — no cooling required

Deploy in electrical rooms, telecom shelters, and edge sites that exceed VRLA operating limits — without adding dedicated cooling infrastructure to support the UPS replacement.

Two Li90 30kVA units at an installation site — rear panel showing fans and input, output, and bypass breakers on the left; front panel with 4.3-inch touchscreen on the right
Two Li90 units at an installation site — rear panel shows fans, input/output breakers, and bypass connections; the front panel with the 4.3″ touchscreen is on the right.
VRLA Replacement

Li90 30kVA vs. traditional 30kVA VRLA UPS systems

Many facilities running legacy 30kVA VRLA UPS systems — including the Eaton 93E, Vertiv EXS, and APC Galaxy VS — are managing external battery cabinets that consume floor space and require replacement every 3–5 years. The Li90 provides a direct replacement path with significantly reduced footprint, weight, and lifecycle cost.

FeatureLi90 30kVATypical 30kVA VRLA UPS
Cabinet width12.6″24–36″
System weight~483 lbs900–1,500 lbs
Battery locationInternal LiFePO₄External cabinets
Battery service lifeUp to 15 years3–5 years
Operating temperature50°C25–30°C
Floor loadingDramatically lowerHigh — may require structural work
Installation complexityLow — single cabinetHigh — UPS plus battery cabinets
Battery serviceHot-swap — no downtimeDowntime planning required
Lifecycle costLowerHigher — recurring replacement

Legacy replacement models: Eaton 93E · Vertiv EXS · APC Galaxy VS. Full competitive comparisons on the Li90 competitive comparison hub →

Platform Features

Li90 30kVA features

Li90 4.3 inch color touchscreen showing the single-line mimic diagram with bypass, rectifier, inverter, and output stages and operating data
The 4.3″ touchscreen — single-line mimic, phase voltages, frequency, event logging, and ON/OFF/EPO controls

Online double-conversion — zero transfer time

Output is regenerated through the inverter at all times. No transfer delay during utility events. Clean, regulated, isolated output power regardless of input conditions.

50°C operation — harsh and unconditioned environments

Reliable operation to 50°C (122°F) without derating until 40°C. Telecom shelters, industrial electrical rooms, edge data centers, and outdoor equipment rooms where VRLA systems are not viable without supplemental cooling.

Hot-swappable LiFePO₄ — 3 modules required

The 30kVA model requires all 3 battery modules — up to 15 minutes runtime at 30kW, 18 minutes at 25kW. Modules are replaced without tools and without powering down the load. Up to 15-year battery service life.

4.3″ touchscreen · SNMP · dry contacts

Color touchscreen with single-line mimic, event log, and security control. Two SNMP/Web card slots. Programmable dry contacts (1 in / 5 out) for facility and BMS integration.

Maintenance bypass — integrated

Input, output, bypass, and maintenance-bypass breakers all integrated in the cabinet. Safe on-site servicing without powering down the load. No external switchgear required.

Conformal-coated PCBs — industrial environments

Circuit boards are conformal coated for industrial and high-humidity environments. The smart self-cleaning fan system extends service life in dusty or contaminated-air environments.

Technical Specifications

Li90 30kVA specifications

Rated power30 kVA / 30 kW
TopologyOnline double-conversion
Input voltage208/120V · 3-phase
Output voltage208/120V · 3-phase
Battery chemistryLiFePO₄ (lithium iron phosphate)
Battery module capacity50 Ah / 57.6 V / 2,880 Wh · 80 lbs each
Battery modules3 required (hot-swappable)
Internal runtime15 min at 30kW · 18 min at 25kW
Battery service lifeUp to 15 years ideal conditions · 3,000–5,000 cycles
Operating temperatureUp to 50°C (122°F) · no derating to 40°C
Cabinet width12.6″ — narrowest 30kVA available
System weight~483 lbs
Battery locationInternal — no external cabinets required
Overload110% for 60 min · 150% for 1 min
Display4.3″ color touchscreen · single-line mimic · event log
Communication2 slots — optional SNMP/Web · dry contacts (1 in / 5 out)
ApprovalsUL 1778 · UN 38.3 · UL 1973 · not currently cUL
Warranty2-year on-site UPS · 5-year battery (USA · up to 40°C)
Applications

Li90 30kVA deployment environments

Li90 Family

Li90 three-phase lithium UPS — all capacities

10kW
Up to 45 min runtime · 1–3 modules · edge and telecom
View 10kW →
20kW
Up to 22 min runtime · 2–3 modules · facility and mid-tier
View 20kW →
30kW
15 min runtime · 3 modules required · slimmest 30kVA available
← current page