5 kVA / 5 kW | 208-240 VAC | Online Double Conversion | 1U
1U online UPS for 208-240 V racks on a 30 A L6-30 circuit. Choose 1U lithium iron phosphate or 2U sealed lead-acid battery packs, up to 5 per UPS, with optional maintenance bypass and isolation PDUs. Available March 2027.
1U Rack · Online Double Conversion · Lithium or Lead-Acid · 208–240V · 5 kW
Available March 2027
The J90 5kW extends the J90 family to 5000 VA / 5000 W at 208–240 V. The UPS is 1U and runs on a 30 A circuit, with an L6-30P input and two L6-30R outputs. Runtime comes from external battery packs, and you choose the chemistry: 1U lithium iron phosphate battery packs for the smallest, lightest system with up to 15-year battery life, or 2U sealed lead-acid battery packs for lower first cost. Up to five battery packs can be connected.

Both versions use the same 1U UPS, PDUs and monitoring. The battery pack sets the system height, weight, runtime per battery pack, operating range and warranty.


| Battery option | Lithium (LFP) | Lead-acid (VRLA) |
|---|---|---|
| UPS model (part number) | J90-5k (90001326) | J90-5k (90001326) |
| Battery pack | BPLi1U192A, lithium iron phosphate (LFP) with BMS | BP2U192A, (16) 12 V sealed lead-acid |
| Battery pack rating | 192 VDC, 3 Ah (576 Wh) | 192 VDC, 5 Ah |
| Battery pack height | 1U | 2U |
| Battery pack dimensions (W × D × H) | 17.2 × 20.9 × 1.7 in | 17.2 × 22.8 × 3.4 in |
| Battery pack weight | 34.2 lbs (15.5 kg) | 74.4 lbs (33.7 kg) |
| Battery packs per UPS | Up to 5 | Up to 5 |
| System height with one battery pack | 2U | 3U |
| Runtime at 5 kW, one battery pack | 5.2 min | 3.3 min |
| Recharge time (one battery pack) | 3 hours to 90% | 5 hours to 90% |
| Battery service life | Up to 15 years in ideal conditions | Standard sealed lead-acid service life |
| Operating temperature | 0–50 °C (32–122 °F), no derating | 0–40 °C (32–104 °F) |
| Warranty (USA and Canada) | 6 years electronics, 6 years battery* | 3 years electronics, 3 years battery |
*Lithium warranty is 2 years for continuous operation above 40 °C, and 2 years depot outside the USA and Canada.
The UPS is 1U and 21.9 in deep. Add one 1U lithium battery pack for a 2U system, or one 2U lead-acid battery pack for 3U.
Continuous inverter output, 0 ms transfer, ≤ 2% THD into linear loads, ≥ 0.99 input power factor.
Same UPS, two battery options: 1U LFP battery packs with BMS, or 2U sealed lead-acid battery packs. Up to five battery packs either way.
Delivers the full 5000 W up to 50 °C (122 °F) with no derating. Lead-acid systems are rated to 40 °C.
Full 5000 W at 208 V, the most a plug-in UPS can deliver on an L6-30 circuit. L6-30P input cord, (2) L6-30R outputs.
Like the J90 and J90i, the J90 5kW is built in Taiwan for TAA-compliant federal, state and GSA purchases.
UPS specifications are the same for both battery options. Battery details are in the battery options table above.
| Specification | J90-5k |
|---|---|
| Capacity | 5000 VA / 5000 W |
| Topology | Online double conversion |
| Input voltage | 208/220/230/240 VAC, 50/60 Hz auto-sensing |
| Input voltage range | 176–300 VAC at full load; down to 110 VAC at 50% load or less |
| Rated input current | 26 A |
| Input power factor | ≥ 0.99 at full linear load |
| Input connection | 10 ft cord, NEMA L6-30P |
| Output voltage | 208/220/230/240 VAC (selectable), ±1% |
| Output frequency | 50/60 Hz, ±0.5% on battery; frequency converter mode (derated to 60%) |
| Waveform | Pure sine wave: ≤ 2% THD (linear load), ≤ 4% THD (non-linear load) |
| Transfer time | 0 ms, line to battery |
| Output receptacles | (2) NEMA L6-30R on short cords |
| Overload | 105–125% for 1 min; > 125% for 1 s, then transfer to bypass |
| Efficiency | Up to 95% online |
| UPS dimensions (W × D × H) | 17.2 × 21.9 × 1.7 in (438 × 556 × 44 mm), 1U |
| UPS weight | 25.4 lbs (11.5 kg) |
| Humidity | 0–90%, non-condensing |
| Audible noise | < 55 dBA |
| Altitude | 6,500 ft (2,000 m) |
| Communications | USB; intelligent slot for optional SNMP-2PV3 Web/SNMP card or RELAY-MINI dry contact card; EPO input |
| Included | Rack-mount brackets, USB cable, battery cable, user manual; ViewPower software (download) |
| Approvals | UL 1778 / CSA C22.2 No. 107.3 (pending); FCC Part 15 / ICES-003 Class A (pending); RoHS; TAA compliant (made in Taiwan). Lithium battery pack: UL 1973, UN 38.3 |
| Load protection | $50,000 connected-equipment policy (USA and Canada; register within 10 days) |

Depth is front bracket to rear panel; add 1 in for the front bezel. Specifications are preliminary and subject to change before release.
Lithium: BPLi1U192A battery packs
| Lithium battery packs | 1 kW | 1.5 kW | 2 kW | 2.5 kW | 3 kW | 3.5 kW | 4 kW | 4.5 kW | 5 kW |
|---|---|---|---|---|---|---|---|---|---|
| 1 battery pack | 19 | 16 | 13 | 10 | 8.6 | 7.8 | 7.1 | 6.1 | 5.2 |
| 2 battery packs | 42 | 35 | 29 | 22 | 19 | 17 | 15 | 13 | 11 |
| 3 battery packs | 63 | 53 | 43 | 34 | 28 | 26 | 23 | 20 | 16 |
| 4 battery packs | 86 | 73 | 59 | 46 | 39 | 35 | 32 | 27 | 22 |
| 5 battery packs | 109 | 92 | 75 | 58 | 49 | 45 | 41 | 34 | 28 |
Lead-acid: BP2U192A battery packs
| Lead-acid battery packs | 1 kW | 1.5 kW | 2 kW | 2.5 kW | 3 kW | 3.5 kW | 4 kW | 4.5 kW | 5 kW |
|---|---|---|---|---|---|---|---|---|---|
| 1 battery pack | 30 | 18 | 12 | 9 | 6 | 4.9 | 4.1 | 3.7 | 3.3 |
| 2 battery packs | 69 | 42 | 30 | 23 | 18 | 14 | 12 | 10 | 9 |
| 3 battery packs | 107 | 69 | 48 | 37 | 30 | 25 | 20 | 18 | 15 |
| 4 battery packs | 137 | 97 | 69 | 52 | 42 | 35 | 30 | 26 | 23 |
| 5 battery packs | 178 | 115 | 90 | 69 | 55 | 46 | 39 | 34 | 30 |
Typical runtimes at 25 °C with new batteries.
| Model | Type | Details | Dimensions (W × D × H) | Weight |
|---|---|---|---|---|
| BPLi1U192A | Lithium battery pack | 192 VDC, 3 Ah LFP, 1U; up to 5 per UPS | 17.2 × 20.9 × 1.7 in | 34.2 lbs |
| BP2U192A | Lead-acid battery pack | 192 VDC, 5 Ah, (16) 12 V VRLA, 2U; up to 5 per UPS | 17.2 × 22.8 × 3.4 in | 74.4 lbs |
| XPD50 | Rear-panel PDU | Plugs into a UPS L6-30R output (12 in L6-30P cord); (2) L6-20R with 20 A breakers, (2) L6-30R | 17.2 × 3.0 × 1.7 in | 6.3 lbs |
| XBDM-J90A | Rear-panel PDU with maintenance bypass | 6 ft L6-30P input; short links to UPS input and output; (2) L6-20R with 20 A breakers, (2) L6-30R; Normal/Bypass switch; RJ11 communication link to the UPS | 17.2 × 4.7 × 1.95 in | 9.0 lbs |
| XPD-IT60A | Isolation transformer PDU | 208/240 V in, isolated 240/120 V out; (12) 5-15/20R, (1) L6-30R | 17.3 × 18.0 × 3.5 in (2U) | 137 lbs |
| SNMP-2PV3 | Web/SNMP card | SNMP, HTTP, Modbus TCP and BACnet; mini slot | ||
| RELAY-MINI | Dry contact card | Relay contacts with DB9 and terminal block adapter |
4-post rail kit and 2-post shelf kit also available.
Outlets and maintenance bypass
Typically mounts on the rear rails (front or vertical mounting also possible) and plugs into an L6-30R on the UPS. Adds (2) L6-20R outlets with 20 A breakers and (2) L6-30R outlets for servers, switches and rack PDUs. Built in Taiwan and TAA compliant.
Typically mounts on the rear rails (front or vertical mounting also possible) and sits between the wall and the UPS, with the same outlets plus a Normal/Bypass switch and an RJ11 link that tells the UPS to transfer to internal bypass when the switch is turned, so the load moves to utility power without a break. Turn the switch to Bypass to feed the load from utility power, then service, replace or upgrade the UPS while equipment stays on. Built in Taiwan and TAA compliant.
The J90 5kW is scheduled to ship in March 2027, with lithium and lead-acid battery packs. Contact sales@xpcc.com to plan projects or reserve units ahead of release.
Choose lithium (BPLi1U192A) for the smallest footprint, lowest weight, longest battery life and operation to 50 °C: each battery pack is 1U and 34 lbs, rated for up to 15 years, with a 6-year warranty. Choose lead-acid (BP2U192A) for lower first cost in a cooled room: each battery pack is 2U and 74 lbs, with a 3-year warranty.
No. The 1U UPS carries the power electronics only, and runtime comes from external battery packs. Up to five battery packs of one type can be connected.
At 5 kW, one lithium battery pack gives about 5 minutes and one lead-acid battery pack about 3 minutes. Five battery packs give about 28 minutes (lithium) or 30 minutes (lead-acid) at 5 kW, and much longer at lighter loads. See the runtime tables on this page.
A 208–240 V circuit with a NEMA L6-30 receptacle. The UPS is rated 5 kVA so it runs on a 30 A circuit; rated input current is 26 A. Output is two L6-30R receptacles, or add an XPD50 or XBDM-J90A for L6-20R and more L6-30R outlets.
Yes. The J90 5kW is rated 5000 VA / 5000 W across 208, 220, 230 and 240 V output. That is as much as a plug-in UPS can draw from a 30 A L6-30 circuit. Many 6 kVA UPSs on an L6-30P cord deliver about 4,600 to 5,000 W at 208 V; their full 6 kW rating needs hardwired input on a larger circuit. With lithium battery packs it delivers the full 5000 W up to 50 °C ambient.
The J90 (120 V) and J90i (208–240 V) cover 1 to 3 kVA with internal lithium batteries and individually switchable outlets. The J90 5kW extends the family to 5 kW at 208–240 V with external battery packs and L6-30R outputs.
Yes. The J90 5kW is built in Taiwan and is TAA compliant for federal, state and GSA purchases, like the J90 and J90i. The XPD50 PDU and XBDM-J90A bypass PDU are also built in Taiwan and TAA compliant; the optional XPD-IT60A isolation PDU is not.
Yes, with the optional XBDM-J90A maintenance bypass PDU. Its 6 ft L6-30P cord goes to the wall receptacle, short cords link it to the UPS input and output, an RJ11 cable connects it to the UPS, and your equipment plugs into its (2) L6-20R and (2) L6-30R outlets. To service or replace the UPS, turn the switch from Normal to Bypass. The RJ11 link tells the UPS to transfer to its internal bypass first, so the load moves to utility power without a break. Then unplug and swap the UPS, and switch back to Normal. The UPS also has an internal automatic bypass that carries the load if it detects a fault or overload.
With lithium battery packs: 6 years electronics and 6 years battery in the USA and Canada, reduced to 2 years for continuous operation above 40 °C, and 2 years depot outside the USA and Canada. With lead-acid battery packs: 3 years electronics and 3 years battery in the USA and Canada. A $50,000 connected-equipment protection policy applies in the USA and Canada when the unit is registered within 10 days.
Send us the load, voltage and runtime target. Our applications team will recommend lithium or lead-acid, size the battery packs and options, and quote the J90 5kW ahead of release.