• SNMP-EMD Environmental Monitoring Device

M90 Modular Online Three Phase UPS

15kVA-60kVA

208/120VAC Three Phase

Mission Critical Availability while reducing costs with Scalable M90 Online UPS for 15kVA, 20kVA, 30kVA, 40kVA, 45kVA, 60kVA applications.

The M90 is a scalable modular online three phase UPS that protects critical data and equipment from power problems, while supplying clean and reliable network grade power.

The M90 can be configured with a fully redundant power module and battery modules. Should one module fail, the remaining modules smoothly take over the load. Because the power modules are independent, they can be hot swapped without risk to the critical load.
As power requirements change, M90 modularity makes it easy to add modules and increase capacity.

Product Snapshot

  • Six capacities: 15kVA/13.5kW, 20kVA/18kW, 30kVA/27kW, 40kVA/36kW, 45kVA/40.5kW, 60kVA/54kW
  • Modular for capacity or redundancy
  • Hot swappable power modules
  • Up to 98% ECO mode or 94% online efficiency
  • Remote control and monitoring options
  • 2 year electronics, 2 year battery warranty (USA and Canada)

To receive a quote on M90 Modular Online Three Phase UPS contact a sales representative at sales@xpcc.com

M90 has many advantages over competitive units: Eaton Blade UPS, Eaton 93PM, Liebert APM, Liebert EXM, Socomec Modulys GP UL, Tripplite SV, Toshiba 4400, Mitsubishi 1100, APC Symmetra PX.  See below link for comparisons

M90 Vs Competition

[table colalign=”left|left|center|center|center|center|center|center”]

,MODEL NUMBER, M90-15, M90-20, M90-30, M90-40, M90-45, M90-60

INPUT,Capacity, 15kVA (13.5kW), 20kVA (18kW), 30kVA (27kW), 40kVA (36kW), 45kVA (40.5kW), 60kVA (54kW)

,Nominal,208/120V 50/60Hz auto sensing[attr colspan=”6″]

,Range,121-253VAC*(L-L) 40-70Hz[attr colspan=”6″]

OUTPUT,Voltage,208/120VAC[attr colspan=”6″]

,Frequency,50/60 ± 0.05Hz [attr colspan=”6″]

,THD (full load),0.9[attr colspan=”6″]

,Voltage regulation,<2%[attr colspan=”6″]

,Efficiency,”98% ECO mode, ≥ 94% online mode”[attr colspan=”6″]

,Overload capacity,105%-110% for 60 min;110%-125% for 10min; 126%-150% for 1min; <150% for 200ms [attr colspan=”6″]

BATTERY SYSTEM,Nominal voltage,±120V[attr colspan=”6″]

,Temperature compensation,Yes with optional sensor [attr colspan=”6″]

,Charging current (programable),8A,16A,24A,8A,16A,24A

PHYSICAL,Enclosure,20.3″W x 39.4″D x 54″H/484 lbs [attr colspan=”6″]

,Power module,19.0”W x 28.0”D x 5.1”H / 74 lbs  [attr colspan=”6″]

,Battery module, 4.1”W x 28.3”D x 6.0”H / 68 lbs [attr colspan=”6″]

ENVIRONMENT,Temperature,0–40°C (32–104°F) [attr colspan=”6″]

,Altitude,”5,200 ft above sea level”[attr colspan=”6″]

,Audible noise, < 65dBA at 1m [attr colspan=”6″]

APPROVALS,,”UL-1778 (TUV), cUL, FCC A, RoHS”[attr colspan=”6″]

WARRANTY,,”2 years (USA and Canada)”[attr colspan=”6″]

COMMUNICATIONS INTERFACE,,”RS-232, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus)” [attr colspan=”6″]

INCLUDED IN BOX,,”User manual, RS-232 cable, Ramp for unloading UPS enclosure”[attr colspan=”6″]

AVAILABLE OPTIONS,,”External maintenance bypass, 480V input transformer, output distribution, battery temperature sensor”[attr colspan=”6″]

[/table]

     

  1. Connectivity

    [table colwidth=”75″]
    ,Model,Description,Unit Weight, Unit Dimensions
    ,SNMP-2P3,Internal Web/SNMP Card,1 lb,7.25″ x 6″ x 2.5
    ,SNMP-EMD,Internal Web/SNMP Card,1 lb,7.25″ x 6″ x 2.5

     

     

    [/table]

  2.  

  3. Skirt Kit

    [table colwidth=”75″]
    ,Model,Description,Unit Weight, Unit Dimensions
    ,M90 SKIRT,Skirt Kit for M90 frame,20 lbs,7” x 43.5” x 6.5”

     

    [/table]