Li90 vs Vertiv Liebert APM2 30 kW Lithium-Ion
The Xtreme Power Li90-30K and the Vertiv Liebert APM2 30 kW with internal lithium-ion batteries are both online double-conversion, unity power factor UPS for 208 V three-phase loads, and both give about 15 minutes at 30 kW. They differ in size and battery design: the Li90 does it in less than half the floor area and weight, with LFP batteries and suppression in every module, while the APM2 is a modular frame that grows to 60 kW, offers N+1 power modules, and takes up to 40 minutes of internal runtime.
What the Li90 brings
- Less than half the floor area (3.1 vs 6.6 sq ft) and 30 in shorter
- Less than half the weight (533 vs 1,101 lbs shipping)
- Lithium iron phosphate chemistry, vs NCA in the APM2
- Suppression capsules built into every battery module
- Batteries rated to 50 °C (122 °F), vs 40 °C
- Battery life up to 15 years, vs 10 to 12 years expected
- Integrated maintenance bypass as standard, with dual input
- Longer overload ride-through (110% for 60 min vs 125% for 10 min)
- Start-up and 2 years on-site service included in the USA
Side-by-side specifications at 30 kW
| Specification | Xtreme Power Li90-30K | Vertiv Liebert APM2 30 kW Li-ion | Advantage / consideration |
|---|---|---|---|
| Topology | Online double conversion, unity PF | Online double conversion, unity PF | Equal protection |
| Capacity | 30 kVA / 30 kW tower | 30 kVA / 30 kW | Equal |
| Modularity | Hot-swap battery modules; single 30 kW power stage | Hot-swap power, bypass, control and battery modules; 2 x 15 kW power modules in a frame that grows to 60 kW; add a third for N+1 | APM2 – modular power and N+1 |
| Input / output | 208/220 V 3-phase, 4W + G; dual input | 208/220 V 3-phase, 4W + G | Equal |
| Battery chemistry | Lithium iron phosphate (LFP) + BMS | NCA (nickel cobalt aluminum ternary lithium) | Li90 – LFP thermal stability |
| Internal battery | 3 hot-swap modules, 8.64 kWh | 3 hot-swap modules, about 9.6 kWh | Equal |
| Battery service life | Up to 15 years in ideal conditions; 3,000 to 5,000 cycles | 10 to 12 years expected; no cycle rating published | Li90 – longer battery life |
| Runtime at 30 kW | 15 min (3 modules, internal max) | 15 min with 3 modules; up to 40 min with 8 | APM2 – longer internal runtime |
| Suppression in battery module | 5 passive heat-activated capsules per module | None built in; room protection recommended | Li90 – built-in suppression |
| Battery operating temperature | To 50 °C (122 °F) | 0 to 40 °C (104 °F) | Li90 – rated to 50 °C |
| W x D x H | 12.6 x 35.2 x 49.2 in | 23.6 x 40.5 x 78.7 in | Li90 – less than half the floor area |
| Shipping weight | 533 lbs | 1,101 lbs (2 power, 3 Li-ion modules) | Li90 – less than half the weight |
| Maintenance bypass | Integrated (standard) | Optional internal breakers or separate cabinet | Li90 – integrated bypass standard |
| Efficiency (30 kVA) | Up to 94.5% online; 99% ECO | 93.5% online at full load, 95.0% peak; 98.4% ECO | Equal |
| Overload (online) | 110% for 60 min; 130% for 10 min; 155% for 1 min | 125% for 10 min; 150% for 1 min | Li90 – longer overload |
| Display | 4.3 in color touchscreen | 9 in color touchscreen | APM2 – larger display |
| Listings | UL 1778; UL 1973 modules; UN 38.3 (not cUL) | UL 1778, CSA | APM2 – Canada (CSA) |
| Standard warranty (USA) | Start-up included; 2 years on-site; 5-year battery | 1-year limited | Li90 – start-up and 2 years on-site |
Li90-30K3 with three battery modules against a 208 V APM2 10 to 60 kVA frame rated 30 kW with three internal lithium-ion modules. Shipping weights with domestic packaging; Li90 installed weight is 485 lbs. Runtimes vary with battery age, temperature and load. Specifications based on manufacturer documentation as of November 2026; confirm against current vendor data. Vertiv and Liebert are trademarks of Vertiv Group Corp.
Choosing between them
The Li90 leads on footprint, weight, battery chemistry and suppression, battery temperature, integrated bypass, overload and included service; the APM2 offers room to grow to 60 kW, modular power with N+1 redundancy, longer internal runtime and CSA listing for Canada. Efficiency is close: both run about 94 to 95% online and 98 to 99% in ECO mode.
Choose the Li90 if you need
- 30 kW or less, with about 15 minutes to bridge to a generator
- A 12.6 in wide tower for a tight electrical or IT room
- Light floor loading: 485 lbs installed with batteries
- LFP batteries with suppression inside each module
- Operation in warm rooms, to 50 °C
- Integrated maintenance bypass without external switchgear
- Start-up and 2 years on-site service included
The Vertiv Liebert APM2 may fit if you need
- Growth past 30 kW in the same frame (to 60 kW at 208 V)
- Modular power with N+1 redundancy
- More than 15 minutes of internal runtime (up to 40 min at 30 kW)
- A site in Canada
- Alignment with an existing Vertiv fleet
Frequently asked questions
Is the Li90-30K an alternative to a 30 kW Liebert APM2 with lithium-ion batteries?
What battery chemistry does each use?
How much runtime do I get at 30 kW?
Which has the better warranty?
Is the Li90 UL listed?
Related comparisons
Quoting against an APM2?
Send us the load, voltage and runtime target. Our applications team will confirm the Li90 fit and send a quote.