Three-Phase Lithium UPS · 10kW–30kW · Internal Batteries · 50°C

Li90 — Compact Three-Phase Lithium UPS with Internal LiFePO₄ Batteries

The Li90 replaces the traditional three-phase UPS plus external battery cabinet combination with a single slim tower. LiFePO₄ batteries are integrated inside the enclosure — no external cabinets, no floor space for battery frames. Available in 10kW, 20kW, and 30kW.

15 yr
Battery service life
ideal conditions · 3,000–5,000 cycles
50°C
Max operating temp
derating above 40°C
12.6″
Cabinet width
slim footprint · no external cabinets
5 yr
Battery warranty
USA · up to 40°C ambient
Li90 three-phase lithium UPS deployed in an electrical room alongside distribution panel — slim 12.6 inch cabinet next to full-size electrical infrastructure
Li90 deployed in an electrical room — the single-cabinet architecture visible alongside distribution panels. No external battery cabinets required.
Three capacities — one platform

Li90 model lineup — 10kW, 20kW, 30kW

All three Li90 models share the same internal battery architecture, cabinet design, and operating specifications. The difference is capacity and the number of battery modules supported. If you’re between sizes, talk to an engineer before specifying — runtime requirements often drive the decision more than load size.

10kW
Li90 · 10 kVA / 10 kW · 208/120V

Distributed and small electrical rooms. Edge and telecom infrastructure where footprint is constrained. Supports 1–3 battery modules.

Internal runtime
15 min at 10kW · 1 module
30 min at 10kW · 2 modules
45 min at 10kW · 3 modules
87 min at 5kW · 3 modules
View 10kW model →
20kW
Li90 · 20 kVA / 20 kW · 208/120V

Facility and mid-tier infrastructure. Industrial automation control rooms and distributed IT environments. Supports 2–3 battery modules.

Internal runtime
15 min at 20kW · 2 modules
22 min at 20kW · 3 modules
View 20kW model →
30kW
Li90 · 30 kVA / 30 kW · 208/120V

Central IT and core infrastructure. Highest capacity in the Li90 family — 3 battery modules required. Slimmest and lightest 30kVA UPS available at ~483 lbs.

Internal runtime
15 min at 30kW · 3 modules
18 min at 25kW · 3 modules
View 30kW model →
Platform architecture

Internal batteries — no external cabinets required

Conventional three-phase UPS systems require separate external battery cabinets — enclosures that consume additional floor space, require additional electrical connections, and complicate installation. The Li90 integrates up to three LiFePO₄ battery modules inside the lower section of the UPS enclosure. The footprint is the UPS. That’s it.

Li90 three-phase lithium UPS with battery door open showing three hot-swappable LiFePO4 battery modules inside the lower cabinet section — no external battery cabinets required
Battery door open — three hot-swappable LiFePO₄ modules inside the lower cabinet. No external battery frames. No additional floor space.
Runtime data

Runtime by load and battery module configuration

Runtime scales with the number of battery modules installed. All three models accept up to 3 modules. The 10kW model can operate with 1 module; the 20kW requires a minimum of 2; the 30kW requires all 3.

Battery modules 5kW 10kW 15kW 20kW 25kW 30kW
1 module 29 min 15 min
2 modules 58 min 30 min 20 min 15 min
3 modules 87 min 45 min 30 min 22 min 18 min 15 min

Runtimes in minutes at continuous load. Approximate — varies by battery age, temperature, and site conditions. Each battery module is 50AH / 57.6V / 2,880Wh · 80 lbs · hot-swappable.

Platform features

Designed for demanding deployment environments

Temperature
50°C operation — no cooling dependency

Rated for continuous operation to 50°C (122°F) without derating until 40°C. Deploy in telecom shelters, industrial rooms, and electrical spaces where VRLA systems require supplemental cooling or capacity reduction.

Battery
Hot-swappable LiFePO₄ modules

Modules are replaced without tools and without powering down the load. LiFePO₄ chemistry supports up to 15 years service life in ideal conditions and 3,000–5,000 charge cycles — significantly longer than VRLA.

Monitoring
4.3″ touchscreen LCD

Full-color touchscreen with single-line mimic diagram, event logging, and security access control. Two communication slots for optional SNMP/Web cards. Programmable dry contacts — 1 input, 5 output — for facility integration.

Protection
Full breaker design with maintenance bypass

Input, output, bypass, and maintenance bypass breakers integrated in the cabinet. Maintenance bypass enables safe on-site servicing without powering down the load. No external switchgear required.

Overload
110% for 60 min · 150% for 1 min

High overload capacity handles startup surges from motors, compressors, and inductive loads without nuisance tripping or transfer to bypass. Appropriate for industrial and facility environments with variable load profiles.

Durability
Conformal coated PCBs · smart de-dust fans

Circuit boards are conformal coated for enhanced durability in industrial and high-humidity environments. Smart de-dust fan system is self-cleaning — reduces maintenance requirements and extends system service life in dusty environments.

VRLA replacement

Li90 vs traditional three-phase VRLA UPS systems

Li90 slim 12.6 inch cabinet installed in electrical room alongside full-size distribution panels and server racks — compact footprint advantage clearly visible
Li90 slim cabinet alongside distribution panels — the 12.6″ width is clearly visible against full-size electrical infrastructure
Feature Li90 lithium platform Typical VRLA three-phase UPS
External battery cabinetsNone — batteries internalRequired for extended runtime
Cabinet width12.6″24–36″
System weight (30kW)~483 lbs900–1,500 lbs
Battery service lifeUp to 15 years3–5 years
Operating temperature50°C25–30°C
Battery serviceHot-swap — no downtimeDowntime planning required
MaintenanceMinimal — no replacement cyclesHigh — recurring replacement
Lifecycle costLowerHigher
Applications

Where the Li90 is deployed

Telecom and distributed infrastructure
Industrial lithium UPS →
Industrial automation and control rooms
Industrial automation UPS →
Edge and space-constrained data centers
Edge data center UPS →
Hospitality, casino, and commercial infrastructure
Retail and edge UPS →
Harsh environments and high-temperature locations
Harsh environment UPS →
Pro AV — stadiums, arenas, broadcast facilities
Pro AV UPS →
Documentation and warranty

Engineering documents

Warranty: 2-year on-site UPS system warranty including startup (USA only). 5-year battery warranty covering standard use up to 40°C ambient (USA only). Approvals: UL1778 · UL38.3 · UL1973. Not currently cUL listed for Canada — confirm approvals status for Canadian deployments.

Talk to an engineer about the Li90

Model selection, runtime sizing, VRLA replacement guidance, installation planning, and battery module configuration.