• XBDM-1520HW Hardwire Bypass Distribution Module
  • XBDM-HW30 Hardwire Bypass Distribution Module
  • XBDM-HW63 Hardwire Bypass Distribution Module

XBDM HW Bypass Distribution Module

15A, 20A, 30A, 63A

XBDM HW provides UPS maintenance bypass with input and output hardwired terminal block connections.

← All products

Hardwired Maintenance Bypass · Terminal-Block I/O

XBDM HW Bypass Distribution Module

The XBDM HW provides UPS maintenance bypass with hardwired terminal-block input and output. Transfer critical loads from UPS power to utility power with a single bypass switch — so the UPS can be repaired or replaced without ever dropping the load.

Ratings
15 · 20 · 30 · 63 A
Connections
Hardwired
terminal-block input & output
Transfer time
8 ms
0 ms on 63A make-before-break
Warranty
3 years
USA & Canada

Overview

Continuous uptime for your critical electronics

The XBDM HW lets you manually transfer critical loads from UPS power to utility power using a bypass switch, enabling UPS repair or replacement without power interruption to the load. Transferring back to protected UPS power is just as easy — simply return the bypass switch to the UPS position.

Available in 15A, 20A, and 30A 120VAC ratings plus a 230VAC/63A model, the XBDM HW uses hardwired terminal-block connections for both utility input and system output. The 15A and 20A models add six 5–15R output receptacles and source-availability LED indicators, and keep connected loads surge protected even when the UPS is in bypass mode.

63A model: the XBDM-HW63 provides make-before-break transfer and a static-switch interlock, and is intended for use with a bypass-interlock UPS.

Features

Built for clean, code-compliant installs

Terminal-block connections

Hardwired input and output terminal blocks for direct connection to utility and load.

Power distribution

The 15A and 20A models also provide six 5–15R output receptacles for connected equipment.

Simple to operate

LED indicators on the 15A and 20A models verify availability of UPS and utility sources at a glance.

Surge protection

Loads stay surge protected on the 15A and 20A models even in bypass mode; UPS electronics are protected during normal operation.

Static-switch interlock

The 63A model provides make-before-break transfer and an interlock for the UPS static switch.

Flexible mounting

Wall and 19″ rack mounting hardware is included in the box.

How it works

Two modes of operation

A single bypass switch moves your critical loads between protected UPS power and direct utility power. Output to the connected loads always comes from the XBDM HW — so you can service or swap the UPS without ever dropping the load.

The XBDM features twomodes of operation:1) Utility modeUtility power bypasses theUPS system and is suppliedto the load directly2) UPS modePower is routed throughthe UPS system to theconnected load Utility modeCONNECTED LOADS UPS modeCONNECTED LOADS
Power path in each mode: in Utility mode, power bypasses the UPS and feeds the connected loads directly; in UPS mode, it routes through the UPS for full protection.

1) Utility mode

Utility power bypasses the UPS system and is supplied to the load directly — used while the UPS is serviced or replaced.

2) UPS mode

Power is routed through the UPS system to the connected load — the normal, fully protected operating state.

Available models

Four ratings, one bypass design

XBDM-15RHW
15 A · 120 VAC

Terminal-block I/O plus six 5–15R receptacles, LED indicators, and surge protection.

XBDM-20RHW
20 A · 120 VAC

Terminal-block I/O plus six 5–15R receptacles, LED indicators, and surge protection.

XBDM-HW30
30 A · 120 VAC

Hardwired terminal-block input and output with a 30A/1P input breaker.

XBDM-HW63
63 A · 230 VAC

Make-before-break transfer with static-switch interlock and a 63A/2P input breaker.

Specifications

Model selection guide

XBDM HW model selection guide. Confirm fit against your UPS rating and connection type before ordering.
Model number XBDM-15RHW XBDM-20RHW XBDM-HW30 XBDM-HW63
Voltage / current 120 VAC / 15 A 120 VAC / 20 A 120 VAC / 30 A 230 VAC / 63 A
Utility input Hardwired terminal block Hardwired terminal block Hardwired terminal block Hardwired terminal block
Input breaker N/A N/A 30A / 1P 63A / 2P
Output Terminal block + (6) 5–15R Terminal block + (6) 5–15R Hardwired terminal block Hardwired terminal block
Transfer switch 20A break-before-make rocker 30A break-before-make rocker 30A break-before-make rotary 63A make-before-break rotary w/ interlock
Transfer time 8 ms 8 ms 8 ms 0 ms
UPS input connection 5–20R 5–20R L5–30R Hardwired or cable kit w/ Anderson connectors
UPS output connection 3 ft cord, 5–15P plug 3 ft cord, 5–20P plug 3 ft cord, L5–30P plug Hardwired or cable kit w/ Anderson connectors
AC surge 6500 A, 114 J, 330 VAC 6500 A, 114 J, 330 VAC 6500 A, 114 J, 330 VAC N/A
LED indicators Utility, surge, UPS Utility, surge, UPS N/A N/A
Dimensions (W×D×H) 17 × 3.5 × 1.75 in 17 × 3.5 × 1.75 in 17 × 3.5 × 1.75 in 17.25 × 5.25 × 3.5 in
Weight 3.6 lbs 3.6 lbs 7.3 lbs 7.1 lbs

*XBDM-HW63 to be used with a bypass-interlock UPS.

Warranty
3 years (USA and Canada).
Included in box
Standard 19″ rack mounting hardware and user manual.
Indicators
UPS available · Utility available · Surge protection (15A / 20A models)
Available options
Input cord sets and connectors, power output receptacles, and source-availability indicator lights.

Where the XBDM HW fits

Hot-swap UPS service without downtime

Network & server protection

Keep racks energized while a UPS is serviced in place.

Network infrastructure UPS →

Edge & distributed IT

Hardwired bypass for compact edge and distributed deployments.

Edge data center UPS →

Industrial & process equipment

Maintain ride-through on PLCs and production-line systems during UPS service.

Industrial automation UPS →

Documents

Datasheets & references

REFXBDM HW product pageView →
REFPlug & receptacle XBDM modelsView →

Related products

Bypass and UPS platforms

Spec the right bypass for your install

Tell us your UPS rating and connection type and we’ll confirm the correct XBDM HW model and cable kit.

[table colalign=”left|left|center|center|center|center “]

,MODEL NUMBER,XBDM-15RHW,XBDM-20RHW,XBDM-HW30,XBDM-HW63*

POWER RATING,Voltage/current,120VAC/15A,120VAC/20A,120VAC/30A,230VAC/63A

INPUT,Utility input,Hardwired terminal block[attr colspan=”4″]

,Breaker,N/A[attr colspan=”2″],30A/1P,63A/2P

OUTPUT,Output,Hardwired terminal block + (6) 5–15R[attr colspan=”2″],Hardwired terminal block[attr colspan=”2″]

TRANSFER SWITCH,Capacity,20A break before make rocker switch[attr colspan=”2″],30A break before make rotary switch,63A make before break rotary switch w/ interlock

,Transfer time,8ms[attr colspan=”2″],8ms,0ms

UPS INPUT,Input connection,5–20R[attr colspan=”2″],L5–30R,Hardwired or cable kit w/ Anderson connectors

UPS OUTPUT,Connection to UPS output,3 ft cord with5–15P plug,3 ft cord with5–20P plug,3 ft cord with L5–30P plug,Hardwired or cable kit w/ Anderson connectors

AC SURGE,Capacity,”6500A, 114J, 330VAC”[attr colspan=”2″],N/A[attr colspan=”2″]

INDICATORS,LED indicators,”Utility, surge, UPS”[attr colspan=”2″],N/A[attr colspan=”2″]

PHYSICAL,Dimensions (W x D x H),17 x 3.5 x 1.75 in[attr colspan=”2″],17.25 x 5.25 x 3.5 in[attr colspan=”2″]

,Weight,3.6 lbs[attr colspan=”2″],7.3 lbs,7.1 lbs

WARRANTY,,3 years (USA and Canada) [attr colspan=”4″]

INCLUDED IN BOX,,”Standard 19 in rack mounting hardware, user manual”[attr colspan=”4″]

AVAILABLE OPTIONS,,Input cord sets and connectors[attr colspan=”4″]

[/table]