Vision REVO TP Series LFP Battery Cabinets



Battery Cabinet · LFP · X90 UPS · 40–700 kW

Vision REVO TP Series LFP Battery Cabinets

The Vision REVO TP Series is a lithium iron phosphate battery system that XPC integrates with the X90 UPS family. All four models use the same cabinet, 23.6 by 39.4 by 78.7 inches, and differ only in the battery modules inside: 20.5 kWh to 51.2 kWh of energy on a ±204.8 Vdc or ±256 Vdc bus, and up to eight cabinets parallel on one system for 410 kWh. Cabinets install and service from the front only and are UL 9540A tested with no thermal runaway or propagation. XPC supplies the cabinets, the firmware integration to the X90, start-up, and warranty support as a single system.

Vision REVO TP battery cabinet front view with door closed, LCD human machine interface mounted on the door

Front view. LCD human machine interface on the door gives direct access to battery status and diagnostics.

Vision REVO TP200 cabinet with door removed showing ten stacked LFP battery modules, breaker, and battery management unit

TP200 with door removed. Ten LFP modules under a single breaker and battery management unit.

410
kWh per system
20.5 to 51.2 kWh per cabinet

200 kW
Max UPS per cabinet
to 700 kW paralleled

2,500
Cycles
100% DOD at 77°F

8
Cabinets paralleled
one GBMS per system

UL
Certification
1973 certified · 9540A tested

5 yr
Parts warranty
2 yr labor with XPC UPS

Key features

Built for the room the UPS actually lives in

Chemistry

LFP cells selected for thermal stability

Lithium iron phosphate trades some energy density for a far more forgiving thermal profile. UL 9540A testing produced no thermal runaway and no propagation, which is the result that matters to the authority having jurisdiction reviewing your installation.

Cabinet

One cabinet across all four models

TP80 through TP200 are the same enclosure at 23.6 x 39.4 x 78.7 in. Only the modules inside change, so energy scales without changing the floor plan and a capacity revision late in design does not move walls or re-cut a raised floor. Weight is the one physical difference, from 1,058 to 1,985 lbs.

Service access

Front access only, no rear clearance

Installation and maintenance are done entirely from the front, and all power and communication cabling enters through the top. Cabinets can sit against a wall, which recovers aisle depth in constrained rooms.

Architecture

Eight or ten rack mounted 51.2 V modules

Each cabinet holds 8 or 10 modules at 50 Ah or 100 Ah, each with its own management unit reporting to the cabinet BMS. Automatic cell balancing holds capacity consistent across the string and extends usable life.

Monitoring

CBMS per cabinet, one GBMS per system

Every cabinet ships with a Cabinet Battery Management System. One Global Battery Management System is required per battery system and ships integrated into the front door of the first cabinet, aggregating every paralleled cabinet into a single reporting point with display, LAN, dry contacts, and EPO.

Integration

Split DC bus, direct to X90

Supports ±204.8 Vdc and ±256 Vdc bus configurations and communicates with the X90 UPS through the GBMS. Up to eight cabinets parallel on one system, with active current distribution balancing load across them.

System integration

Integration with the X90 family

The TP Series is a third-party battery system, not an XPC-manufactured product. Pairing high energy density lithium cabinets from a specialist battery manufacturer with a UPS platform is standard practice across the industry, and it is how the large UPS vendors bring lithium to market. What differs between vendors is the depth of the integration and who stands behind the combined system. XPC supplies the TP Series as an integrated part of an X90 system: sized together, commissioned together, and supported under one warranty.

Firmware

Validated firmware pairing

Battery firmware is field upgradable. XPC validates GBMS and CBMS firmware against X90 control firmware and documents the combinations we support, so a battery firmware revision does not arrive at a live site untested against the UPS.

Battery state

The X90 reads the battery, not just its voltage

The GBMS presents state of charge, cell and module data, and alarm conditions to the UPS. Charge current limits and the charge voltage window are set to the cabinet model rather than to a generic lead-acid profile.

Protection

EPO and dry contacts tied to the system

The GBMS provides an EPO contact and three dry contacts that land in the X90 and the facility monitoring scheme, so a battery event is visible and actionable at the UPS and at the building.

Commissioning

One start-up for UPS and battery

When the TP Series is purchased with an XPC UPS and start-up, commissioning covers both. That is also the condition for the two year labor warranty on the battery system.

Sizing

Sized against the DC load, not the kVA badge

Cabinet count is set by DC load and target runtime, then checked against the discharge current ceiling of the model. A DC collector cabinet may be required depending on cabinet count and installation.

Support

One number for the whole system

Service escalation runs through XPC for both the UPS and the battery system. Customers are not routed between a UPS vendor and a battery vendor to establish which one owns a fault.

Model selection

Four capacities, one cabinet

The four models share one enclosure and differ in module count and module capacity. TP80 and TP160 hold eight modules, TP100 and TP200 hold ten, and the 50 Ah or 100 Ah module rating sets the energy. Select on energy and on the maximum UPS capacity a single cabinet supports, then parallel cabinets to reach the runtime the load requires. Up to eight cabinets can be paralleled on one system. Cabinets pair by nominal voltage: TP80 and TP160 run a ±204.8 Vdc bus, TP100 and TP200 run ±256 Vdc. Each cabinet is supplied as a bundle with its battery modules and CBMS. Battery modules ship on a separate pallet.

TP80
20.5 kWh · ±204.8 Vdc
Modules 8 x 51.2 V / 50 Ah
Capacity 50 Ah
Max UPS 80 kW
Max discharge 250 A
Weight 1,058 lbs

Entry

TP100
25.62 kWh · ±256 Vdc
Modules 10 x 51.2 V / 50 Ah
Capacity 50 Ah
Max UPS 100 kW
Max discharge 250 A
Weight 1,213 lbs
TP160
41.0 kWh · ±204.8 Vdc
Modules 8 x 51.2 V / 100 Ah
Capacity 100 Ah
Max UPS 180 kW
Max discharge 510 A
Weight 1,676 lbs
TP200
51.2 kWh · ±256 Vdc
Modules 10 x 51.2 V / 100 Ah
Capacity 100 Ah
Max UPS 200 kW
Max discharge 510 A
Weight 1,985 lbs

Highest energy

A DC collector cabinet may be required depending on cabinet count and UPS installation. We will confirm the requirement when we size the system.

Request sizing →

Runtime data

Runtime in minutes by DC load and cabinet configuration

Values are estimated minutes at the DC load shown, for a new battery at rated capacity. Actual runtime varies with battery age, ambient temperature, and site conditions. The table shows selected load points. Use the finder for any load in 10 kW steps from 40 kW to 700 kW. Runtimes are published up to four cabinets. For configurations above four cabinets, contact XPC engineering.

Configuration 40
kW
50
kW
60
kW
80
kW
100
kW
120
kW
150
kW
200
kW
250
kW
300
kW
350
kW
400
kW
500
kW
600
kW
700
kW
TP80 27.6 23.0 18.4 13.8
2 x TP80 55.2 46.0 36.8 27.6 22.1 18.4 14.7
3 x TP80 82.8 69.0 55.2 41.4 33.1 27.6 22.1 16.6
TP100 34.5 28.8 23.0 17.3 13.8
2 x TP100 69.0 57.5 46.0 34.5 27.6 23.0 18.4 13.8
3 x TP100 104 86.3 69.0 51.8 41.4 34.5 27.6 20.7 16.6 13.8
TP160 55.2 46.0 36.8 27.6 22.1 18.4 14.7
2 x TP160 110 92.0 73.6 55.2 44.2 36.8 29.4 22.1 17.7 14.7 12.9
3 x TP160 166 138 110 82.8 66.2 55.2 44.2 33.1 26.5 22.1 19.3 16.6 13.2
TP200 69.0 57.5 46.0 34.5 27.6 23.0 18.4 13.8
2 x TP200 138 115 92.0 69.0 55.2 46.0 36.8 27.6 22.1 18.4 16.1 13.8
3 x TP200 207 172 138 104 82.8 69.0 55.2 41.4 33.1 27.6 24.2 20.7 16.5 13.8
4 x TP200 276 230 184 138 110 92.0 73.6 55.2 44.1 36.8 32.2 27.6 22.0 18.4 14.8

All values in estimated minutes. A dash means the configuration does not support that load. X90 UPS → · Request a sized configuration →

Full specifications

Vision REVO TP Series specifications

Specification TP80 TP100 TP160 TP200
Energy 20.5 kWh 25.62 kWh 41.0 kWh 51.2 kWh
Capacity 50 Ah 50 Ah 100 Ah 100 Ah
Nominal voltage ±204.8 Vdc ±256 Vdc ±204.8 Vdc ±256 Vdc
Module configuration 8 x 51.2 V / 50 Ah 10 x 51.2 V / 50 Ah 8 x 51.2 V / 100 Ah 10 x 51.2 V / 100 Ah
Recommended charge current 10 A to 25 A
Maximum charge current 25 A 25 A 50 A 50 A
Charge voltage ±217.6 to ±220.8 Vdc ±272 to ±276 Vdc ±217.6 to ±220.8 Vdc ±272 to ±276 Vdc
Maximum discharge current at EODV 250 A 250 A 510 A 510 A
Maximum supported UPS capacity 80 kW 100 kW 180 kW 200 kW
Discharge end point voltage ±179.2 Vdc ±224 Vdc ±179.2 Vdc ±224 Vdc
Dimensions W x D x H 23.6 x 39.4 x 78.7 in (599 x 1,000 x 1,999 mm)
Weight 1,058 lbs 1,213 lbs 1,676 lbs 1,985 lbs
Operating temperature 32°F to 104°F (0°C to 40°C)
Cycle life 2,500 cycles at 77°F, 0.5C / 2C, 100% DOD
Cabinet access Front access only. No rear clearance required. Top cable entry.
Communications Dry contact, CANBUS, MODBUS to X90 UPS
Cabinet BMS Cabinet Battery Management System (CBMS) included with every cabinet
System BMS One GBMS required per battery system, factory integrated into the first cabinet
Maximum cabinets paralleled 8
Shipping Battery modules ship on a separate pallet from the cabinet
Warranty 5 year parts. Start-up and 2 year labor warranty when purchased with an XPC UPS and start-up.
Compliance and safety IEC 62619, UL 9540A, UL 1973,
CE (EN 62477, EN 62040), CE-EMC (IEC 61000-6-2)
IEC 62619, IEC 60068, UL 9540A, UL 1973,
CE (EN 62477, EN 62040), CE-EMC (IEC 61000-6-2)

Required accessory

Vision GBMS

One Global Battery Management System is required for each Vision battery system. It communicates with every paralleled battery cabinet, the UPS, and the user. The GBMS ships integrated into the front door of the first cabinet, so there is no separate enclosure to mount or wire on site.

Vision GBMS Specification
Function Communicates with all parallel battery cabinets, the UPS, and the user
Interfaces Display, LAN interface, 3 dry contacts, EPO contact
Mounting Factory integrated into the front door of the first cabinet
Quantity required One per battery system

Certifications and documents

Compliance

UL 1973
UL 9540A
IEC 62619
IEC 60068
CE EN 62477
CE EN 62040
CE-EMC IEC 61000-6-2

IEC 60068 applies to the TP160 and TP200. UL 9540A testing was performed with no thermal runaway and no propagation observed.

Specify a REVO TP system

Send the UPS model, DC load, and target runtime. We return a cabinet count, floor space, collector cabinet requirement, and lead time.

MODEL NUMBER TP80 TP100 TP160 TP200
CABINET Energy 20.5 kWh 25.62 kWh 41 kWh 51.2 kWh
Capacity 50 AH 50 AH 100 AH 100 AH
Nominal Voltage ±204.8 Vdc ±256 Vdc ±204.8 Vdc ±256 Vdc
Battery Modules 8 × 51.2V 50AH 10 × 51.2V 50AH 8 × 51.2V 100AH 10 × 51.2V 100AH
Cabinet BMS CBMS included with every cabinet
CHARGING Charge Current, Recommended 10 A to 25 A
Charge Current, Maximum 25 A 25 A 50 A 50 A
Charge Voltage ±217.6 to ±220.8 Vdc ±272 to ±276 Vdc ±217.6 to ±220.8 Vdc ±272 to ±276 Vdc
DISCHARGING Max Discharge Current at EODV 250 A 250 A 510 A 510 A
Max Supported UPS Capacity 80 kW 100 kW 180 kW 200 kW
Discharge End Point Voltage ±179.2 Vdc ±224 Vdc ±179.2 Vdc ±224 Vdc
SYSTEM Maximum Cabinets Paralleled 8
System BMS One GBMS required per Vision Lithium Battery System
Communication Dry contact, CANBUS, MODBUS to X90 UPS
MECHANICAL Dimensions (W × D × H) 23.6 × 39.4 × 78.7 in (599 × 1,000 × 1,999 mm)
Weight 1,058 lbs 1,213 lbs 1,676 lbs 1,985 lbs
Access Front access only, no rear clearance required. Top cable entry.
ENVIRONMENTAL Operating Temperature 32°F to 104°F (0°C to 40°C)
Life Cycle 2,500 cycles at 77°F, 0.5C / 2C, 100% DOD
APPROVALS Compliance Safety IEC62619, UL9540A, UL1973, CE(EN62477, 62040), CE-EMC(IEC61000-6-2)
Warranty 5 year parts. Start-up and 2 year labor warranty when purchased with an XPC UPS and start-up.